The gate valve is the oldest isolation design still in widespread use, and for good reason. Fully open, it leaves an almost unobstructed bore and causes very little pressure loss. Fully closed, a wedge or a pair of discs sits across the flow path and is held against two seats. It is robust, available in every material and pressure class, and familiar to every fitter. It is also, by a long way, the valve most often abused by being used to regulate flow, and that abuse ruins it.
What a gate valve is designed to do
A gate valve has two positions in its design brief. Open, the gate is withdrawn completely into the bonnet. Closed, the gate is driven down between the seats, and the sealing load comes from stem thrust wedging it between two inclined seat faces, helped on the downstream side by line pressure pushing the gate onto the downstream seat.
For steel gate valves in refinery and petrochemical service the main reference is API 600 for bolted bonnet valves, with API 602 covering compact forged steel valves in small bore and API 603 covering corrosion resistant, light wall valves. Pressure ratings follow ASME B16.34. In water distribution, resilient seated gate valves with a rubber encapsulated wedge are standard, and in pulp, mining and slurry work, knife gate valves use a sharpened blade to cut through solids.
Nothing in that brief covers an intermediate position. The guides that locate the gate are loose fits, meant to keep it aligned on its way down, not to hold it steady in a flowing stream.
What happens to a gate held partly open
Close a gate valve part of the way and the flow is forced under the bottom edge of the gate through a crescent shaped opening. Several things go wrong at once.
First, the flow characteristic is very poor. For most of the travel the gate barely affects the flow, because the opening remains large compared with the pipe. Nearly all the useful reduction happens in the last part of the stroke, where a small turn of the handwheel produces a large change in flow. Fine adjustment is impossible, and the valve ends up set very close to closed, which is the worst place for it.
Second, the seat faces erode. The high velocity jet passes directly across the lower part of both seats and the bottom edge of the gate. In clean water this produces wire drawing, fine channels cut across the seating faces. In steam or flashing service the damage is faster, and with solids present the seats are cut in a short time. These are the same surfaces that must later seal for isolation, so a throttled gate valve destroys its only real function. The fitter who next tries to isolate the line for maintenance finds the valve passing.
Third, the gate vibrates. Held part way in a stream with loose guides, it is pushed against the downstream seat, released as the flow fluctuates and pushed again. It chatters against guides and seats, wears the guide slots and gate edges and loosens the joint between stem and gate. In severe cases the gate parts from the stem and drops, leaving the valve stuck wherever the gate settles.
Fourth, in liquid service, the pressure drop across a nearly closed gate can be high enough to cavitate, pitting the downstream seat and body wall in exactly the area that is hardest to repair.
Wedge designs and the problems they solve
Gate valves have failure modes of their own even when they are used correctly, and the choice of wedge is the main defence.
- Solid wedge. Strong and simple and suited to most services, but it can be gripped between the seats if a valve closed hot cools and the body contracts around it. That is thermal binding.
- Flexible wedge. A single piece with a groove cut around its perimeter so the two faces can flex slightly. It accommodates seat distortion from pipe loads and temperature changes and is the usual choice on steam and hot oil.
- Split wedge or parallel disc. Two separate discs that align themselves to the seats. They tolerate distortion well but can rattle in flowing service.
Pressure locking is the other serious hazard. Liquid trapped in the bonnet cavity of a closed valve can be heated and expand, or can simply be left at a pressure above the line on either side. That pressure then forces both seat faces against the gate so hard that the operator or actuator cannot lift it. In nuclear plant the problem was serious enough to prompt regulatory action in the United States. The usual remedy is a small hole through the upstream face of the wedge, or an external bypass from the bonnet to the upstream side. Either makes the valve unidirectional, so the flow arrow must be respected.
Operating a gate valve correctly
Open fully, close fully and nothing in between, apart from the brief crack used to warm a steam line or equalise pressure. For steam warming, and for large valves with high differential pressure, a small bypass valve around the gate is far better than cracking the main gate. The bypass, usually a globe valve, takes the throttling punishment and is cheap to replace.
On a rising stem outside screw and yoke valve, back the handwheel off slightly after opening fully. Driving the stem hard against the backseat and leaving it there makes the valve appear seized to the next person, and in hot service the stem can bind after thermal expansion. Use the backseat deliberately when repacking under pressure, and only where the valve design and plant procedure allow it.
Closing is a matter of feel. Wedge seating takes stem thrust, and overtightening with a valve key or cheater bar damages seats and bends stems. On actuated valves the torque or thrust limit must be set to the manufacturer’s value, never raised to force a sticking valve, which only hides the real fault until something breaks.
When the temptation to throttle appears
It usually appears because no throttling valve was provided and somebody needs less flow. The correct fix is to install a globe valve, a characterised ball valve or a control valve in the right place, or to trim the pump impeller or slow the pump with a variable speed drive. A gate valve marked as normally throttled on a piping and instrumentation diagram should prompt a design change, not acceptance.
The same thinking applies to commissioning, when gate valves are often cracked to fill and vent lines. Brief use of that kind does little harm on clean water. Leaving the valve in that position for weeks while the plant runs does real harm.
The gate valve is a very good isolation valve. Kept fully open or fully closed, it will give tight shutoff after decades of service. Used as a regulator, it turns into a leaking valve that can no longer isolate anything.